Inspection #: 351385
Inspection Type: Final Plumbing
Inspector: H8
Result: Correction
Comment: 9 am please Requested by: Shane perrins 230-6544 shanemperrins@gmail.com Requested by: Shane perrins 230-6544 shanemperrins@gmail.com Rest of plumbing final approved. CCO EXPIRES 4-28-15. Correction: Comments Correction: Comments Correction: Comments Correction: Comments Correction: Comments Correction: Comments

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
4/14/2015TransferPlumbFinalCommentsSee Inspector CommentsHand sink drain tail piece exceedes 24'' waste must be raised Per UPC Section 910.5. 
4/14/2015TransferPlumbFinalCommentsSee Inspector Commentsprovide support on indirect wastes & air gaps at open waste receptors PER UPC Section 801.1-801.2 on all required indirect drains. 
4/14/2015TransferPlumbFinalCommentsSee Inspector CommentsKitchen equipment is not complete. 
4/14/2015TransferPlumbFinalCommentsSee Inspector CommentsProtect copper water lines through contrete slab PER Section 313.10.1 
4/14/2015TransferPlumbFinalCommentsSee Inspector CommentsSecure dishwasher & kitchen sinks to the wall, caulk all fixtures. 
4/14/2015TransferPlumbFinalCommentsSee Inspector CommentsReplace sheilded coupling with approved transtion coupling on dishwasher tray. 