Date | Status | Code | Description | Ref | Location | Comments |
7/7/2015 | Transfer | Fire 2 | CCO approval | Fire Final approved for CCO | | Fire Alarm system/permit to be CO'd with operational handshake completed to Building fire alarm system. |
7/7/2015 | Transfer | Fire 2 | CCO approval | Fire Final approved for CCO | | Addressing - both at mall entrances both floor levels, consistant with mall practices & on exit corridor doors is required. |
7/7/2015 | Transfer | Fire 2 | CCO approval | Fire Final approved for CCO | | Emergency lighting - add cans which are on order in those areas that appeared deficient upon power loss testing; will test again on CO inspection. |
7/7/2015 | Transfer | Fire 2 | CCO approval | Fire Final approved for CCO | | CCO for permission to begin moving in stock only with conditions: 1) 24/7 hr. Security on site, walking site, hourly log kept, they are the Fire Watch. |
7/7/2015 | Transfer | Fire 2 | CCO approval | Fire Final approved for CCO | | 2) Finish all construction for CO |
7/7/2015 | Transfer | Correct Below | * | | | 2) Finish all construction for CO |
7/7/2015 | Transfer | Fire 2 | CCO approval | Fire Final approved for CCO | | Door(s) to rear exit/egress - remove "inoperable" -Push to exit button(s) & card slider access readers - egress can't be compromised for private access. |
7/7/2015 | Transfer | Fire 2 | CCO approval | Fire Final approved for CCO | | Overhead rolling door egress & emergency release mechanisms to be tested upon final CO (or prior to); |
7/7/2015 | Transfer | Fire 2 | CCO approval | Fire Final approved for CCO | | Obtain Elevator CO & Escalator CO & structural CO for guardrail around escalator shaft; Cordon this area off until CO obtained. |