Inspection #: 350939
Inspection Type: Final Fire Inspection
Inspector: H8
Result: Partial
Comment: CALL SEAN 909-919-0415 30 MINS BEFORE ||

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/7/2015TransferFire 2CCO approvalFire Final approved for CCO Fire Alarm system/permit to be CO'd with operational handshake completed to Building fire alarm system.
7/7/2015TransferFire 2CCO approvalFire Final approved for CCO Addressing - both at mall entrances both floor levels, consistant with mall practices & on exit corridor doors is required.
7/7/2015TransferFire 2CCO approvalFire Final approved for CCO Emergency lighting - add cans which are on order in those areas that appeared deficient upon power loss testing; will test again on CO inspection.
7/7/2015TransferFire 2CCO approvalFire Final approved for CCO CCO for permission to begin moving in stock only with conditions: 1) 24/7 hr. Security on site, walking site, hourly log kept, they are the Fire Watch.
7/7/2015TransferFire 2CCO approvalFire Final approved for CCO 2) Finish all construction for CO
7/7/2015TransferCorrect Below*  2) Finish all construction for CO
7/7/2015TransferFire 2CCO approvalFire Final approved for CCO Door(s) to rear exit/egress - remove "inoperable" -Push to exit button(s) & card slider access readers - egress can't be compromised for private access.
7/7/2015TransferFire 2CCO approvalFire Final approved for CCO Overhead rolling door egress & emergency release mechanisms to be tested upon final CO (or prior to);
7/7/2015TransferFire 2CCO approvalFire Final approved for CCO Obtain Elevator CO & Escalator CO & structural CO for guardrail around escalator shaft; Cordon this area off until CO obtained.