Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 345154
Inspection Type: Final Electrical
Inspector: M.Green
Result: Approved
Comment: Contact Bob @ 727-2002 prior to arrival. Inspection to include remaining H&M store items and the DAC Requested by: Bob Parsons 727-2002 bob@qealaska.com H & M store core and shell, and Dimond Center Athletic Club misc remodel. H&M store feeder breaker key access issue has been passed on this electrical permit. Providing key access to the H&M store feeder breaker is now a condition added to the H&M store electrical T/I permit. RTU related items resolved by ETL field evaluation.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
3/27/2015 EF1Correct Below RTU aux fan units.#10 cords feeding aux fan units terminated under RTU main lugs with #6 building wire.
3/27/2015 EF1Correct Below Basement electrical room witth breaker feeding H&M Store.Sub feed breaker for H&M Store is in a restricted access area in BSMT under athletic club. Each occupant must have ready access to all OCPDs feeding his occupancy per 240.24(B).
3/27/2015 EF1Correct Below RTUsMaybe other issues.
3/27/2015 EF1Correct Below New item. 2nd fl sales area.(3) exit signs not coming on with power failure.
3/27/2015 EF1Correct Below New item. Lighting circuits with upsized current carrying conductoors.Upsize equipment ground wires per 250.122(B).
3/27/2015 EF1Correct Below Old item. RTU aux fan unitsTrane RTUs fed by 40-60A ckts. #10 cords feeding aux fan units without apparent OCPD.
3/27/2015 EF1Correct Below RTU aux fan unitsRTUs are Trane with UL listing. Aux fan units are ThyCurb withno listing, or amp rating.
3/27/2015 EF1Correct Below RTU aux fan units.Aux units come with factory supplied cord which appears intended to hard wire. Cords generally not allowed for hard wiring per NEC.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter