Inspection #: 345154
Inspection Type: Final Electrical
Inspector: M.Green
Result: Approved
Comment: Contact Bob @ 727-2002 prior to arrival. Inspection to include remaining H&M store items and the DAC Requested by: Bob Parsons 727-2002 bob@qealaska.com H & M store core and shell, and Dimond Center Athletic Club misc remodel. H&M store feeder breaker key access issue has been passed on this electrical permit. Providing key access to the H&M store feeder breaker is now a condition added to the H&M store electrical T/I permit. RTU related items resolved by ETL field evaluation.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
3/27/2015 EF1Correct Below RTU aux fan units.#10 cords feeding aux fan units terminated under RTU main lugs with #6 building wire.
3/27/2015 EF1Correct Below Basement electrical room witth breaker feeding H&M Store.Sub feed breaker for H&M Store is in a restricted access area in BSMT under athletic club. Each occupant must have ready access to all OCPDs feeding his occupancy per 240.24(B).
3/27/2015 EF1Correct Below RTUsMaybe other issues.
3/27/2015 EF1Correct Below New item. 2nd fl sales area.(3) exit signs not coming on with power failure.
3/27/2015 EF1Correct Below New item. Lighting circuits with upsized current carrying conductoors.Upsize equipment ground wires per 250.122(B).
3/27/2015 EF1Correct Below Old item. RTU aux fan unitsTrane RTUs fed by 40-60A ckts. #10 cords feeding aux fan units without apparent OCPD.
3/27/2015 EF1Correct Below RTU aux fan unitsRTUs are Trane with UL listing. Aux fan units are ThyCurb withno listing, or amp rating.
3/27/2015 EF1Correct Below RTU aux fan units.Aux units come with factory supplied cord which appears intended to hard wire. Cords generally not allowed for hard wiring per NEC.