Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 343221
Inspection Type: Final Electrical
Inspector: H8
Result: Correction
Comment: Contact John @ 929-1359 when on site Requested by: Bob Parsons 727-2002 bob@qealaska.com Some items from 2/4/2015 not corrected. (2) new items. Only inspected H&M Store. Did not inspect athletic club portion of project. Correction: Correct Below Note: #10 cords feeding aux fan units terminated under RTU main lugs with #6 building wire. Correction: Correct Below Note: Maybe other issues. Correction: Correct Below Note: Sub feed breaker for H&M Store is in a restricted access area in BSMT under athletic club. Each occupant must have ready access to all OCPDs feeding his occupancy per 240.24(B). Correction: Correct Below Note: (3) exit signs not coming on with power failure. Correction: Correct Below Note: Upsize equipment ground wires per 250.122(B). Correction: Correct Below Note: Trane RTUs fed by 40-60A ckts. #10 cords feeding aux fan units without apparent OCPD. Correction: Correct Below Note: RTUs are Trane with UL listing. Aux fan units are ThyCurb withno listing, or amp rating. Correction: Correct Below Note: Aux units come with factory supplied cord which appears intended to hard wire. Cords generally not allowed for hard wiring per NEC.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
       
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter