Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 340805
Inspection Type: Fire Alarm Final
Inspector: C.Burgoyne
Result: Partial
Comment: 5th Ave Mall, Fire Alarm to Elevator interface testing 1/17/2019 Elevator 1 was intermittently not operating due to elevator door issues, however it did respond correctly to one of the primary recall initiating devices (4th floor) and the alternate recall initiating device(1st floor) Elevators 2 through 8 all responded correctly to all initiating devices. Elevator 9 (Sullivan’s) responded correctly to the smoke detectors and recalled to the proper floors. Both heat detectors shunt tripped the main line disconnect for the elevator. Note, there is no sprinkler in this hoistway and therefore the heat detector in the hoistway is not required. Fire and Elevator Inspectors agree the heat detector should not have been installed and shall be eliminated. A primary factor in this determination is the lack of flashing hat with the activation of hoistway or machine room smoke detectors. Additionally the smoke detector is not required in the hoistway for this type of elevator and it may also be eliminated. Elevator 10 (Apple Store) Responded correctly to all initiating devices. Elevator Inspector Curt Burgoyne CEI 3606

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
       
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS