Inspection #: 335420
Inspection Type: Ceiling Rough Electrical
Inspector: O.Burbridge
Result: Partial
Comment: Inspections for grid ceilings where available as well as Final inspections. Requested by: Chris Stafford 830-2507 chriss2cold@gmail.com progress.. Correction: Correct Below Note: bond around knockouts in disconnect for elevator 2 Correction: Correct Below Note: fused disconnect for elevator lighting may not be over edge of housekeeping pad Correction: Correct Below Note: need to verify that Oliver inspected transformer grounding and bonding Correction: Correct Below Note: no apparent third party listing, input and output ratings on VFDs Correction: Correct Below Note: bond around knockouts at disconnect for EF-1 Correction: Correct Below Note: all recptacles must be weather resistant and have extra duty in-use covers Correction: Correct Below Note: bonding bushings at motor controllers Correction: Correct Below Note: basement corridor lens covers must be able to open Correction: Correct Below Note: no power at mens room light Correction: Correct Below Note: breaker lock at facp breaker Correction: Correct Below Note: south bathrooms incomplete Correction: Correct Below Note: remove temp lighting from lids

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
12/11/2014TransferEC1Correct Below basementbasement corridor lens covers must be able to open
12/11/2014TransferEC1Correct Below basementremove temp lighting from lids
12/11/2014TransferEC1Correct Below basementsouth bathrooms incomplete
12/11/2014TransferEC1Correct Below basementbreaker lock at facp breaker
12/11/2014TransferEC1Correct Below basementno power at mens room light
12/11/2014TransferEC1Correct Below basementbonding bushings at motor controllers
12/9/2014TransferEC1Correct Below in penthousebond around knockouts in disconnect for elevator 2
12/9/2014TransferEC1Correct Below in penthousefused disconnect for elevator lighting may not be over edge of housekeeping pad
12/9/2014TransferEC1Correct Below in penthouseneed to verify that Oliver inspected transformer grounding and bonding
12/9/2014TransferEC1Correct Below in penthouseno apparent third party listing, input and output ratings on VFDs
12/9/2014TransferEC1Correct Below on rooftopbond around knockouts at disconnect for EF-1
12/9/2014TransferEC1Correct Below on rooftopall recptacles must be weather resistant and have extra duty in-use covers