Click Here To View Another Inspection Inspection #: 335418 Inspection Type: Ceiling Rough Electrical Inspector: O.Burbridge Result: Partial Comment: Inspections for available ceilings and Final inspections for level 1 and basement where possible. Requested by: Chris Stafford 830-2507 chriss2cold@gmail.com Correction: Correct Below Note: bond around knockouts in disconnect for elevator 2 Correction: Correct Below Note: fused disconnect for elevator lighting may not be over edge of housekeeping pad Correction: Correct Below Note: need to verify that Oliver inspected transformer grounding and bonding Correction: Correct Below Note: no apparent third party listing, input and output ratings on VFDs Correction: Correct Below Note: bond around knockouts at disconnect for EF-1 Correction: Correct Below Note: all recptacles must be weather resistant and have extra duty in-use covers Correction: Correct Below Note: bonding bushings at motor controllers Correction: Correct Below Note: basement corridor lens covers must be able to open Correction: Correct Below Note: no power at mens room light Correction: Correct Below Note: breaker lock at facp breaker Correction: Correct Below Note: south bathrooms incomplete Correction: Correct Below Note: remove temp lighting from lids Inspection Corrections DateStatusCodeDescriptionRefLocationComments