Inspection #: 335120
Inspection Type: Ceiling Rough Electrical
Inspector: D.Rooney
Result: Partial
Comment: Inspection for available ceilings Requested by: Chris Stafford 830-2507 chriss2cold@gmail.com electrical final approved in basement mechanical room, ceiling electrical approved in rooms 114, B-26, B-10 Correction: Correct Below Note: bond around knockouts in disconnect for elevator 2 Correction: Correct Below Note: fused disconnect for elevator lighting may not be over edge of housekeeping pad Correction: Correct Below Note: need to verify that Oliver inspected transformer grounding and bonding Correction: Correct Below Note: no apparent third party listing, input and output ratings on VFDs Correction: Correct Below Note: bond around knockouts at disconnect for EF-1 Correction: Correct Below Note: all recptacles must be weather resistant and have extra duty in-use covers

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
12/1/2014 EC1Correct Below comm roomquad receptacle on right dead
12/1/2014 EC1Correct Below at 5th floor panelsmore detail needed for rooms supplied by more than one circuit, apply arc-flash warning labels
12/1/2014 EC1Correct Below in penthouse panelsidentify circuits supplying emergency and egress lighting