Inspection #: 332774
Inspection Type: Final Electrical
Inspector: D.Rooney
Result: Approved
Comment: Late Am, I am not on site please provide 15 minute notice. Thanks, Nick Requested by: Nick Therrien 9075383431 therrien.nicholas@gmail.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
11/12/2014 EF1Correct Below Stock room switch gear.1-line shows, and install is: #4CU protected by 150A breaker on 480V side. Engineer needs to change dwg. Breaker size needs to be reduced.
11/12/2014 EF1Correct Below Stock room switch gear.1-line shows 100A fused disc. in MDP feeding 100A MCB PNL H. Install is 100A feed to 150A MCB PNL H. Engineer needs to review and change as necessary.
11/12/2014 EF1Correct Below Rooftop.Label AHU
11/12/2014 EF1Correct Below Stock roomBond XFMR secondary to H2O line in area served.