Click Here To View Another Inspection Inspection #: 331582 Inspection Type: FireStopping Inspector: D.Blackburn Result: Partial Comment: Requested by: Barry Lapp 907-229-1706 Barryl@criteriongeneral.com Basement air shaft termination enclosure appears complete exceptdamper flanges arenotinstalled and do not have clearance depth to actuator box from face of GWB 1st level exit enclosure core ceiling framing approved to cover. S. stair shaft wall approved complete core ceiling. Correction: see inspector comments Note: protect against weather and install fire stop assembly for curtain wall/ slab edge per manufacturer requirements Inspection Corrections DateStatusCodeDescriptionRefLocationComments