Inspection #: 330719
Inspection Type: Final Electrical
Inspector: M.Green
Result: Partial
Comment: Please call prior to arrival as I am not on site, 15 min notice will be sufficient Requested by: Nick Therrien 9075383431 therrien.nicholas@gmail.com Conditional electrical final approved until 11-28-2014 to make corrections. Correction: Correct Below Note: 1-line shows, and install is: #4CU protected by 150A breaker on 480V side. Engineer needs to change dwg. Breaker size needs to be reduced. Correction: Correct Below Note: 1-line shows 100A fused disc. in MDP feeding 100A MCB PNL H. Install is 100A feed to 150A MCB PNL H. Engineer needs to review and change as necessary. Correction: Correct Below Note: Label AHU Correction: Correct Below Note: Bond XFMR secondary to H2O line in area served.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/30/2014 EF1Correct Below Branch ckt Panel L1..5A inline fuses to protect meter. Does panel listing allow fuses inside?
10/30/2014 EF1Correct Below MDPMetering CTs inside. Does MDP listing allow this?