Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 329748
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: Re-inspection of final inspections discrepancy. Please notify Bo when on site @ 720-9321 Requested by: Bob Parsons 9077272002 bob@qealaska.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/29/2014TransferEF1Correct Below main hallwaysfloor boxes not complete
10/29/2014TransferEF1Correct Below upstairsinverter for emergency lights needs working clearances
10/29/2014TransferEF1Correct Below upstairsinverter output circuit is an emergency circuit and may not be in same raceway or j-box with input or normal lighting circuits
10/29/2014TransferEF1Correct Below upstairsworking light required in room with panel and inverters for emergency lights
10/29/2014TransferEF1Correct Below upstairsexposed conductors coming out of outlet box must be removed
10/29/2014TransferEF1Correct Below south service corridorexiting not done per plans, submit revised plans for muni approved including exit signs and emergency lights
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter