Date | Status | Code | Description | Ref | Location | Comments |
10/24/2014 | Transfer | EF1 | Correct Below | | upstairs | working light required in room with panel and inverters for emergency lights |
10/24/2014 | Transfer | EF1 | Correct Below | | upstairs | exposed conductors coming out of outlet box must be removed |
10/24/2014 | Transfer | EF1 | Correct Below | | south service corridor | exiting not done per plans, submit revised plans for muni approved including exit signs and emergency lights |
10/24/2014 | Transfer | EF1 | Correct Below | | main hallways | floor boxes not complete |
10/24/2014 | Transfer | EF1 | Correct Below | | upstairs | inverter for emergency lights needs working clearances |
10/24/2014 | Transfer | EF1 | Correct Below | | upstairs | inverter output circuit is an emergency circuit and may not be in same raceway or j-box with input or normal lighting circuits |