Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 329545
Inspection Type: Final Electrical
Inspector: G.Stuller
Result: Approved
Comment: Please final inspect the north/south, east/west corridors and service corridors. Contact Bo when on site so that he can meet you. @ 720-9321 Requested by: Bob Parsons 727-2002 Bob@qealaska.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/24/2014TransferEF1Correct Below upstairsworking light required in room with panel and inverters for emergency lights
10/24/2014TransferEF1Correct Below upstairsexposed conductors coming out of outlet box must be removed
10/24/2014TransferEF1Correct Below south service corridorexiting not done per plans, submit revised plans for muni approved including exit signs and emergency lights
10/24/2014TransferEF1Correct Below main hallwaysfloor boxes not complete
10/24/2014TransferEF1Correct Below upstairsinverter for emergency lights needs working clearances
10/24/2014TransferEF1Correct Below upstairsinverter output circuit is an emergency circuit and may not be in same raceway or j-box with input or normal lighting circuits
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter