Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 328700
Inspection Type: Final Mechanical
Inspector: R.Larson
Result: Approved
Comment: Structural and Seismic inspection of RTU's for CO. Requested by: Jim Letts 907-947-2318 jletts@sheetmetalinc.biz

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/21/2014 MechFinal16Deferred SubmittalsDeferred submittals are required for rooftop equipment- AMC23.10.104.8.122 RTU"SProvide deferred submitals for roof top equipment in excess of 400lbs.
10/16/2014 MechFinalSee commentsSee Inspector CommentsApproved plans to be on jobsite for inspections. 
10/16/2014 MechFinalSee commentsSee Inspector CommentsRoof top gas pipingUnion in middle of gas run prohibited. See IFGC 403.10.4 ( Left right nipple and coupling)
10/16/2014 MechFinalSee commentsSee Inspector CommentsGas piping to be tagged with unit/suite number 
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS