Inspection Type: Final Mechanical
Inspector: R.Larson
Result: Partial
Comment: Plumbing/Gas Inspection. Please call 15 min. prior to arrival. Requested by: Charlie Neff 907-444-4886

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/16/2014TransferMechFinalSee commentsSee Inspector CommentsApproved plans to be on jobsite for inspections. 
10/16/2014TransferMechFinalSee commentsSee Inspector CommentsRoof top gas pipingUnion in middle of gas run prohibited. See IFGC 403.10.4 ( Left right nipple and coupling)
10/16/2014TransferMechFinalSee commentsSee Inspector CommentsGas piping to be tagged with unit/suite number 
10/16/2014TransferMechFinal16Deferred SubmittalsDeferred submittals are required for rooftop equipment- AMC23.10.104.8.122 RTU"SProvide deferred submitals for roof top equipment in excess of 400lbs.