Inspection #: 327513
Inspection Type: Final Mechanical
Inspector: R.Larson
Result: Correction
Comment: Please call 15 minutes prior to arrival. Thanks. Requested by: Thomas Eli 841-3115 jletts@sheetmetalinc.biz

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/14/2014TransferMechFinalSee commentsSee Inspector CommentsApproved plans to be on jobsite for inspections. 
10/14/2014TransferMechFinalSee commentsSee Inspector CommentsGas piping to be tagged with unit/suite number 
10/14/2014TransferMechFinal16Deferred SubmittalsDeferred submittals are required for rooftop equipment- AMC23.10.104.8.122 RTU"SProvide deferred submitals for roof top equipment in excess of 400lbs.
10/14/2014TransferMechFinalSee commentsSee Inspector CommentsRoof top gas pipingUnion in middle of gas run prohibited. See IFGC 403.10.4 ( Left right nipple and coupling)