| Date | Status | Code | Description | Ref | Location | Comments |
| 10/3/2014 | Transfer | ES1 | Correct Below | see inspectors comment | Feeder j-box under trailer. | There are 4 insulated conductors in feeder from meter stack. Use 1 wire as EGC, and 1 as neutral. Identify accordingly. |
| 10/3/2014 | Transfer | ES1 | Correct Below | see inspectors comment | Feeder j-box under trailer. | Sepparate EGCs, neutrals, and GEC. |
| 10/3/2014 | Transfer | ES1 | Correct Below | see inspectors comment | Feeder j-box under trailer. | Cannot use romex connector on individual cnductors. |
| 10/3/2014 | Transfer | ES1 | Correct Below | see inspectors comment | GEC under trailer. | Must be continuous or spliced with a ''copper c''. |
| 10/3/2014 | Transfer | ES1 | Correct Below | see inspectors comment | Elecrical panel. | Fasten added ground bar to enclosure. |
| 10/3/2014 | Transfer | ES1 | Correct Below | see inspectors comment | Electrical panel. | No more than (2) ground wires per terminal. |