Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 324490
Inspection Type: Electrical Rough
Inspector: H8
Result: Cancel
Comment: Please call 30 min before arriving 9074449344 Keli Requested by: Keli Cross 9074449344 Home owner wanted mech /plumbing inspection. Request for electrical was a mistake.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
9/29/2014TransferEC1Correct Below at parking areaHBH receptacle required GFCI protected, tamper resistant, weather resistant, with in-use cover on dedicated circuit
9/29/2014TransferEC1Correct Below at dryerdryer receptacle and cord must be 4-prong 4-wire
9/29/2014TransferEC1Correct Below at panelhave electricial adjust stand-offs inside panel so cover fits properly
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS