Inspection #: 324319
Inspection Type: Electrical Rough
Inspector: M.Green
Result: Partial
Comment: Failed 1st inspection.. fixed Requested by: Keli Cross 9074449344

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
9/29/2014TransferEC1Correct Below at parking areaHBH receptacle required GFCI protected, tamper resistant, weather resistant, with in-use cover on dedicated circuit
9/29/2014TransferEC1Correct Below at dryerdryer receptacle and cord must be 4-prong 4-wire
9/29/2014TransferEC1Correct Below at panelhave electricial adjust stand-offs inside panel so cover fits properly