Inspection #: 323785
Inspection Type: Electrical Rough
Inspector: D.Rooney
Result: Correction
Comment: AM PLZ - Call Kelly@ 444-9344 1/2hr b4 coming to meet

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
9/26/2014TransferEC1Correct Below at panelhave electricial adjust stand-offs inside panel so cover fits properly
9/26/2014TransferEC1Correct Below at parking areaHBH receptacle required GFCI protected, tamper resistant, weather resistant, with in-use cover on dedicated circuit
9/26/2014TransferEC1Correct Below at dryerdryer receptacle and cord must be 4-prong 4-wire