Date | Status | Code | Description | Ref | Location | Comments |
2/4/2015 | Transfer | ElecRoughOther | 000 Electrical Rough Other | Please correct the following: | Basement electrical room with breaker feeding H and M store. | Feeder disconnect for H and M store is in a restricted access area in BSMT below athletic club. Each occupant must have ready access to all OCPD per 240.24(B). |
2/4/2015 | Transfer | ElecRoughOther | 000 Electrical Rough Other | Please correct the following: | H and M store ceilings. | Existing conduits must be secured per NEC. |
2/4/2015 | Transfer | ElecRoughOther | 000 Electrical Rough Other | Please correct the following: | H and M store RTUs. | Gas lines violate 480V working clearances. |
2/4/2015 | Transfer | ElecRoughOther | 000 Electrical Rough Other | Please correct the following: | H and M store RTU aux fan units. | RTUs are Trane with UL listing. Aux fan units are ThyCurb with no listing mark, UR, or amp rating. Various possible listing issues. |
2/4/2015 | Transfer | ElecRoughOther | 000 Electrical Rough Other | Please correct the following: | H and M RTU aux fan units. | Units come with a factory supplied cord whip which appears intended to hard wire to Trane RTUs. Cords generally not allowed for hard wiring. |
2/4/2015 | Transfer | ElecRoughOther | 000 Electrical Rough Other | Please correct the following: | H and M RTU aux fan units | Trane RTUs are 40-60A rated. Cords feeding aux fan units are #10 with no apparent OCPD. |
2/4/2015 | Transfer | ElecRoughOther | 000 Electrical Rough Other | Please correct the following: | Trane RTUs | #10 cords feeding aux fan units are terminated under main lugs with #6 CU building wire. |
2/4/2015 | Transfer | ElecRoughOther | 000 Electrical Rough Other | Please correct the following: | RTUs | May be other RTU issues. |
2/4/2015 | Transfer | ElecRoughOther | 000 Electrical Rough Other | Please correct the following: | H and M Electrical room transformer | GEC cannot run through metal conduit without bonding at both ends. |