Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 322271
Inspection Type: Electrical Rough
Inspector: H8
Result: Correction
Comment: Notify John @ 929-1359 when on site so that he can meet you Requested by: Bob Parsons 727-2002 bob@qealaska.com. Inspecting elevator wall and roof Requested by: Bob Parsons 907-727-2002 bob@qealaska.com H and M store 1st fl elevator shaft wall electrical rough approved. Other areas of H and M store core and shell have corrections to resolve. Correction: 000 Electrical Rough Other Note: Trane RTUs are 40-60A rated. Cords feeding aux fan units are #10 with no apparent OCPD. Correction: 000 Electrical Rough Other Note: #10 cords feeding aux fan units are terminated under main lugs with #6 CU building wire. Correction: 000 Electrical Rough Other Note: May be other RTU issues. Correction: 000 Electrical Rough Other Note: GEC cannot run through metal conduit without bonding at both ends. Correction: 000 Electrical Rough Other Note: Feeder disconnect for H and M store is in a restricted access area in BSMT below athletic club. Each occupant must have ready access to all OCPD per 240.24(B). Correction: 000 Electrical Rough Other Note: Existing conduits must be secured per NEC. Correction: 000 Electrical Rough Other Note: Gas lines violate 480V working clearances. Correction: 000 Electrical Rough Other Note: RTUs are Trane with UL listing. Aux fan units are ThyCurb with no listing mark, UR, or amp rating. Various possible listing issues. Correction: 000 Electrical Rough Other Note: Units come with a factory supplied cord whip which appears intended to hard wire to Trane RTUs. Cords generally not allowed for hard wiring.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
2/4/2015TransferElecRoughOther000 Electrical Rough OtherPlease correct the following:Basement electrical room with breaker feeding H and M store.Feeder disconnect for H and M store is in a restricted access area in BSMT below athletic club. Each occupant must have ready access to all OCPD per 240.24(B).
2/4/2015TransferElecRoughOther000 Electrical Rough OtherPlease correct the following:H and M store ceilings.Existing conduits must be secured per NEC.
2/4/2015TransferElecRoughOther000 Electrical Rough OtherPlease correct the following:H and M store RTUs.Gas lines violate 480V working clearances.
2/4/2015TransferElecRoughOther000 Electrical Rough OtherPlease correct the following:H and M store RTU aux fan units.RTUs are Trane with UL listing. Aux fan units are ThyCurb with no listing mark, UR, or amp rating. Various possible listing issues.
2/4/2015TransferElecRoughOther000 Electrical Rough OtherPlease correct the following:H and M RTU aux fan units.Units come with a factory supplied cord whip which appears intended to hard wire to Trane RTUs. Cords generally not allowed for hard wiring.
2/4/2015TransferElecRoughOther000 Electrical Rough OtherPlease correct the following:H and M RTU aux fan unitsTrane RTUs are 40-60A rated. Cords feeding aux fan units are #10 with no apparent OCPD.
2/4/2015TransferElecRoughOther000 Electrical Rough OtherPlease correct the following:Trane RTUs#10 cords feeding aux fan units are terminated under main lugs with #6 CU building wire.
2/4/2015TransferElecRoughOther000 Electrical Rough OtherPlease correct the following:RTUsMay be other RTU issues.
2/4/2015TransferElecRoughOther000 Electrical Rough OtherPlease correct the following:H and M Electrical room transformerGEC cannot run through metal conduit without bonding at both ends.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter