Inspection #: 312462
Inspection Type: Final Electrical
Inspector: D.Rooney
Result: Correction
Comment: 9 AM Requested by: Robert 841-8506

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/1/2014TransferEF1Correct Below plansprovide updated plans showing changes to feeders, panels, additional loads and load calculations
8/1/2014TransferEF1Correct Below planssubmit updated plans to MOA for approval
8/1/2014TransferEF1Correct Below transformersecondary side of transformer required main breaker or fused disconnect
8/1/2014TransferEF1Correct Below transformerinstall GEC for transformer, bond to both ends of raceways if in matal raceway
8/1/2014TransferEF1Correct Below transformer primary breakerplans call for 90 amp breaker (100 amp installed)
8/1/2014TransferEF1Correct Below at future flagpole and scoreboardbond raceways and j-box lids
8/1/2014TransferEF1Correct Below under 480 volt panelGEC run through metal raceway must be bonded at both ends or re-route outside of metal raceways
8/1/2014TransferEF1Correct Below in 480 volt panelseparate equipment ground split bolted to grounding electrode conductor