Date | Status | Code | Description | Ref | Location | Comments |
7/21/2014 | Transfer | EF1 | Correct Below | | panel B | breaker ties do not stay on, must be identified for 3-pole use |
7/21/2014 | Transfer | EF1 | Correct Below | | show window | show window receptacles not identified |
7/21/2014 | Transfer | EF1 | Correct Below | | at meters | panels and panel feeders must be marked 149A and 149B |
7/21/2014 | Transfer | EF1 | Correct Below | | Panel A | panel A some circuits marked spare appear to be in use |
7/21/2014 | Transfer | EF1 | Correct Below | | Panel A | ckt a-21 marked front exit sign does not appear to have other lights on it, if so must have thumbscrew type device |