Inspection #: 310505
Inspection Type: Final Electrical
Inspector: D.Rooney
Result: Correction
Comment: late PM Requested by: Stanley 227-9110/ 887-9132

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/21/2014TransferEF1Correct Below panel Bbreaker ties do not stay on, must be identified for 3-pole use
7/21/2014TransferEF1Correct Below show windowshow window receptacles not identified
7/21/2014TransferEF1Correct Below at meterspanels and panel feeders must be marked 149A and 149B
7/21/2014TransferEF1Correct Below Panel Apanel A some circuits marked spare appear to be in use
7/21/2014TransferEF1Correct Below Panel Ackt a-21 marked front exit sign does not appear to have other lights on it, if so must have thumbscrew type device