| Date | Status | Code | Description | Ref | Location | Comments |
| 6/26/2014 | Transfer | EF1 | Correct Below | | hallway outside pub | work not complete |
| 6/26/2014 | Transfer | EF1 | Correct Below | | mechanical room | 25 amp breaker too big for 5.8 amp circ pump p-1 |
| 6/26/2014 | Transfer | EF1 | Correct Below | | at outdoor deck | exit signs need to be outdoor rated |
| 6/25/2014 | Transfer | EF1 | Correct Below | | | |
| 6/25/2014 | Transfer | EF1 | Correct Below | | fan room B | battery backed lights must be on same circuit as normal lights |
| 6/25/2014 | Transfer | EF1 | Correct Below | | comm room in basement | battery backed em light must be on same circuit as normal lighting |
| 6/25/2014 | Transfer | EF1 | Correct Below | | all heat trace | |
| 6/24/2014 | Transfer | EF1 | Correct Below | | fan room A PMP-C9 & c11 | |
| 6/24/2014 | Transfer | ElecRoughOther | 000 Electrical Rough Other | Please correct the following: | on catwalk | |
| 6/24/2014 | Transfer | EF1 | Correct Below | | Area E concessions | provide outlet for refer? |
| 6/24/2014 | Transfer | EF1 | Correct Below | | balcony | em lighting on east and west columns not working |
| 6/9/2014 | Transfer | EF1 | Correct Below | | level 1, area c, aux gym | fans are marked as recognized components not as listed product |
| 6/5/2014 | Transfer | EF1 | Correct Below | | level 1, area c, aux gym | flourescent lights not properly listed and labeled |
| 6/5/2014 | Transfer | EF1 | Correct Below | | level 1, area c, aux gym | |