Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 305017
Inspection Type: Final Electrical
Inspector: M.Green
Result: Partial
Comment: Please call Elliott when on site @ 229-8028 Requested by: Jesse Hale 279-1002 jesse@endeavorak.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
6/26/2014TransferEF1Correct Below PanelsLabel as to source of supply.
6/26/2014TransferEF1Correct Below PanelsNeed arc-flash warning labels.
6/26/2014TransferEF1Correct Below Fabric faced signsConfirm class 2 power source.
6/26/2014TransferEF1Correct Below "Basics" neon signEnclosure not grounded. Check others.
6/26/2014TransferEF1Correct Below "Forever 21" sign disconnect.Hanging on wires.
6/26/2014TransferEF1Correct Below Fabric faced signs.No listing for power supplies. Front fabric sign power supply not in enclosure. No disconnect. Not class 2.
6/26/2014TransferEF1Correct Below Self contained neon sign "21 Men"Not listed?
6/26/2014TransferEF1Correct Below Questionable signs.Keep turned off until issues resolved.
6/26/2014TransferEF1Correct Below XFMR to steel connection.Needs to be accessable.
6/26/2014TransferEF1Correct Below Issues per 6/19/2014.Remain
6/26/2014TransferEF1Correct Below VariousCorrect previous issues.
6/26/2014TransferEF1Correct Below Fabric faced signs, self contained neon signs.Keep off until next inspection.
6/26/2014TransferEF1Correct Below Electrical Room gutters.More than 30 conductors in cross-sectional area.
6/26/2014TransferEF1Correct Below PanelsNeed panel schedules.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter