Date | Status | Code | Description | Ref | Location | Comments |
6/23/2014 | Transfer | EF1 | Correct Below | | Electrical Room gutters. | More than 30 conductors in cross-sectional area. |
6/23/2014 | Transfer | EF1 | Correct Below | | Panels | Need panel schedules. |
6/23/2014 | Transfer | EF1 | Correct Below | | Panels | Label as to source of supply. |
6/23/2014 | Transfer | EF1 | Correct Below | | Panels | Need arc-flash warning labels. |
6/23/2014 | Transfer | EF1 | Correct Below | | Fabric faced signs | Confirm class 2 power source. |
6/23/2014 | Transfer | EF1 | Correct Below | | "Basics" neon sign | Enclosure not grounded. Check others. |
6/23/2014 | Transfer | EF1 | Correct Below | | "Forever 21" sign disconnect. | Hanging on wires. |
6/23/2014 | Transfer | EF1 | Correct Below | | Fabric faced signs. | No listing for power supplies. Front fabric sign power supply not in enclosure. No disconnect. Not class 2. |
6/23/2014 | Transfer | EF1 | Correct Below | | Self contained neon sign "21 Men" | Not listed? |
6/23/2014 | Transfer | EF1 | Correct Below | | Questionable signs. | Keep turned off until issues resolved. |
6/23/2014 | Transfer | EF1 | Correct Below | | XFMR to steel connection. | Needs to be accessable. |
6/23/2014 | Transfer | EF1 | Correct Below | | Issues per 6/19/2014. | Remain |