Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 304954
Inspection Type: Final Electrical
Inspector: D.Rooney
Result: Partial
Comment: Requested by: Bill Hobbins 350-8395 bhobbins@alcanelectric.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
6/20/2014TransferEF1Correct Below on catwalk 
6/20/2014TransferEF1Correct Below Area E concessionsprovide outlet for refer?
6/20/2014TransferEF1Correct Below balconyem lighting on east and west columns not working
6/20/2014TransferEF1Correct Below fan room Bbattery backed lights must be on same circuit as normal lights
6/20/2014TransferEF1Correct Below fan room A PMP-C9 & c11motors are rated 2 amps and lowest setting on overloads is 4 amps, too high
6/20/2014TransferEF1Correct Below comm room in basementbattery backed em light must be on same circuit as normal lighting
6/9/2014TransferEF1Correct Below level 1, area c, aux gymfans are marked as recognized components not as listed product
6/5/2014TransferEF1Correct Below level 1, area c, aux gymflourescent lights not properly listed and labeled
6/5/2014TransferEF1Correct Below level 1, area c, aux gym 
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS