| Date | Status | Code | Description | Ref | Location | Comments |
| 6/12/2014 | Transfer | EF1 | Correct Below | | on catwalk | |
| 6/12/2014 | Transfer | EF1 | Correct Below | | Area E concessions | provide outlet for refer? |
| 6/12/2014 | Transfer | EF1 | Correct Below | | balcony | em lighting on east and west columns not working |
| 6/12/2014 | Transfer | EF1 | Correct Below | | fan room B | battery backed lights must be on same circuit as normal lights |
| 6/12/2014 | Transfer | EF1 | Correct Below | | fan room A PMP-C9 & c11 | motors are rated 2 amps and lowest setting on overloads is 4 amps, too high |
| 6/12/2014 | Transfer | EF1 | Correct Below | | comm room in basement | battery backed em light must be on same circuit as normal lighting |
| 6/9/2014 | Transfer | EF1 | Correct Below | | level 1, area c, aux gym | fans are marked as recognized components not as listed product |
| 6/5/2014 | Transfer | EF1 | Correct Below | | level 1, area c, aux gym | flourescent lights not properly listed and labeled |
| 6/5/2014 | Transfer | EF1 | Correct Below | | level 1, area c, aux gym | |