Inspection #: 3010
Inspection Type: Electrical Inspection
Inspector: M.Curry
Result: Correction
Comment: Interrupting rating on 15 amp breaker must match the installed breakers (100KA) or provide engineer's calculation showing 15 amp breaker is suitable (appears to be 18KA) Dale Rooney