Click Here To View Another Inspection Inspection #: 3010 Inspection Type: Electrical Inspection Inspector: M.Curry Result: Correction Comment: Interrupting rating on 15 amp breaker must match the installed breakers (100KA) or provide engineer's calculation showing 15 amp breaker is suitable (appears to be 18KA) Dale Rooney Inspection Corrections DateStatusCodeDescriptionRefLocationComments