| Date | Status | Code | Description | Ref | Location | Comments |
| 6/5/2014 | Transfer | EF1 | Correct Below | | level 1, area c, aux gym | flourescent lights not properly listed and labeled |
| 6/5/2014 | Transfer | EF1 | Correct Below | | level 1, area c, aux gym | |
| 6/5/2014 | Transfer | EF1 | Correct Below | | on catwalk | contol panel for scoreboard winch not listed and labeled |
| 6/5/2014 | Transfer | EF1 | Correct Below | | level 1, area c, aux gym | fans are marked as recognized components not as listed product |