Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 297986
Inspection Type: Gas Piping Rough
Inspector: R.Larson
Result: Correction
Comment: Requested by: Paul 231-9417 Rest of gas piping rough and test approved. Correction: Gas Regulator Vent Note: To be piped 3' above or 10' horizontaly from any air intake. Correction: Gas Regulator Ports Required Note: Test ports required each side of regulator. IFGC 410.2 #'s 5 & 6

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
12/15/2014TransferGasPipeRgh11Gas Regulator VentGas regulator vent shall be vented to the outside or be equipped with a vent limiting means complying with CSA Z21.80- UPC 1208.7.5.1 (1) exception.RTU 3To be piped 3' above or 10' horizontaly from any air intake.
12/15/2014TransferGasPipeRgh9Gas Regulator Ports RequiredGas regulator requires test ports on inlet/outlet ports- IFGC 410.2 # 5 and 6RTU 3Test ports required each side of regulator. IFGC 410.2 #'s 5 & 6
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS