6/20/2014 | Transfer | EF1 | Correct Below | | Electrical Room gutters. | More than 30 conductors in cross-sectional area. |
6/20/2014 | Transfer | EF1 | Correct Below | | Panels | Need panel schedules. |
6/20/2014 | Transfer | EF1 | Correct Below | | Panels | Label as to source of supply. |
6/20/2014 | Transfer | EF1 | Correct Below | | Panels | Need arc-flash warning labels. |
6/20/2014 | Transfer | EF1 | Correct Below | | Fabric faced signs | Confirm class 2 power source. |
6/20/2014 | Transfer | EF1 | Correct Below | | "Basics" neon sign | Enclosure not grounded. Check others. |
6/20/2014 | Transfer | EF1 | Correct Below | | "Forever 21" sign disconnect. | Hanging on wires. |