Inspection #: 296519
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: Please call Royce @ 792-9602 when on site Requested by: Jesse Hale 279-1002 jesse@endeavorak.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
6/20/2014TransferEF1Correct Below Electrical Room gutters.More than 30 conductors in cross-sectional area.
6/20/2014TransferEF1Correct Below PanelsNeed panel schedules.
6/20/2014TransferEF1Correct Below PanelsLabel as to source of supply.
6/20/2014TransferEF1Correct Below PanelsNeed arc-flash warning labels.
6/20/2014TransferEF1Correct Below Fabric faced signsConfirm class 2 power source.
6/20/2014TransferEF1Correct Below "Basics" neon signEnclosure not grounded. Check others.
6/20/2014TransferEF1Correct Below "Forever 21" sign disconnect.Hanging on wires.