Date | Status | Code | Description | Ref | Location | Comments |
5/12/2014 | Transfer | EF1 | Correct Below | | 1.Bar / serving area. | Mug froster recept K-56 recept not GFCI |
5/12/2014 | Transfer | EF1 | Correct Below | | 2.Bar / serving area | Cash register recept C-8 not GFCI |
5/12/2014 | Transfer | EF1 | Correct Below | | 3.Bar front face receptacles | All within 6 ft of sink need GFCI. |
5/12/2014 | Transfer | EF1 | Correct Below | | 4.Roof top | Strut bracing for cooler / freezer disconnects violates working clearances of smaller unit. |
5/12/2014 | Transfer | EF1 | Correct Below | | 5.Rooftop | Captive Aire elect compartment working clearances violated by photocell on conduit stub. |
5/12/2014 | Transfer | EF1 | Correct Below | | 6.Rooftop | RTU-2, RTU-3 working clearances violated by gas lines. |
5/12/2014 | Transfer | EF1 | Correct Below | | 7.Rooftop | RTU-3 WP recept cover broken. Recept dead. |
5/12/2014 | Transfer | EF1 | Correct Below | | EDC | Label as to feed. |
5/12/2014 | Transfer | EF1 | Correct Below | | Recpt ckt K-43, A-26, M-12, M-19 | Not GFCI |
5/12/2014 | Transfer | EF1 | Correct Below | | Fry warmer | Listing mark? |
5/12/2014 | Transfer | EF1 | Correct Below | | Heated food well | Needs breaker lock |
5/12/2014 | Transfer | EF1 | Correct Below | | Walk-in cooler / freezer | Make up not complete |