Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 296505
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: Meet with Virgil on site for inspection Requested by: Bob Parsons 727-2002 bob@qealaska.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
5/12/2014TransferEF1Correct Below 1.Bar / serving area.Mug froster recept K-56 recept not GFCI
5/12/2014TransferEF1Correct Below 2.Bar / serving areaCash register recept C-8 not GFCI
5/12/2014TransferEF1Correct Below 3.Bar front face receptaclesAll within 6 ft of sink need GFCI.
5/12/2014TransferEF1Correct Below 4.Roof topStrut bracing for cooler / freezer disconnects violates working clearances of smaller unit.
5/12/2014TransferEF1Correct Below 5.RooftopCaptive Aire elect compartment working clearances violated by photocell on conduit stub.
5/12/2014TransferEF1Correct Below 6.RooftopRTU-2, RTU-3 working clearances violated by gas lines.
5/12/2014TransferEF1Correct Below 7.RooftopRTU-3 WP recept cover broken. Recept dead.
5/12/2014TransferEF1Correct Below EDCLabel as to feed.
5/12/2014TransferEF1Correct Below Recpt ckt K-43, A-26, M-12, M-19Not GFCI
5/12/2014TransferEF1Correct Below Fry warmerListing mark?
5/12/2014TransferEF1Correct Below Heated food wellNeeds breaker lock
5/12/2014TransferEF1Correct Below Walk-in cooler / freezerMake up not complete
5/12/2014TransferEF1Correct Below Remote ext EM headNot coming on.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter