Inspection #: 294730
Inspection Type: Final Plumbing
Inspector: M.Gifford
Result: Approved
Comment: Thank you! Requested by: September Cassidy 907-522-8126 cassidysplumbing@aol.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
5/8/2014 PlumbFinalCommentsSee Inspector CommentsASSE 1070 on lavs required 
4/29/2014 PlumbFinalCommentsSee Inspector Commentslavslavs require ASSE1070
4/29/2014 PlumbFinal15Cleanout CapProvide an <u>approved</u> plug or cap for outside cleanout (Econo/Dollar plugs and Jim caps are not approved)- UPC 719.3, 707.1, 707.2 &nbsp;and local amendment UPC 719.1, UPC 719.5  
4/29/2014 PlumbFinal16Future Fixture CapsProvide an approved cap or plug for future plumbing-417.0shower drains 
4/29/2014 PlumbFinal17Backflow Preventer RequiredAn approved backflow preventer is required-UPC 602.2shopPVB required on hb drains in shop
4/29/2014 PlumbFinal5Water Closet SeatWater closet seat is required to be elongated and have an open front-UPC 408.2, 408.2.1 and 408.2.2  
4/29/2014 PlumbFinal6ADA RequirementsFixtures are not installed per ADA requirements-Per ANSI A1171.1 codeback shopflush handle to be outside of wall
4/29/2014 PlumbFinal7Backflow Preventer TestingBackflow preventer shall be tested and properly tagged-UPC 603.1  