| Date | Status | Code | Description | Ref | Location | Comments |
| 4/29/2014 | Transfer | PlumbFinal | Comments | See Inspector Comments | lavs | lavs require ASSE1070 |
| 4/29/2014 | Transfer | PlumbFinal | Comments | See Inspector Comments | ASSE 1070 on lavs required | |
| 4/29/2014 | Transfer | PlumbFinal15 | Cleanout Cap | Provide an <u>approved</u> plug or cap for outside cleanout (Econo/Dollar plugs and Jim caps are not approved)- UPC 719.3, 707.1, 707.2 and local amendment UPC 719.1, UPC 719.5 | | |
| 4/29/2014 | Transfer | PlumbFinal16 | Future Fixture Caps | Provide an approved cap or plug for future plumbing-417.0 | shower drains | |
| 4/29/2014 | Transfer | PlumbFinal17 | Backflow Preventer Required | An approved backflow preventer is required-UPC 602.2 | shop | PVB required on hb drains in shop |
| 4/29/2014 | Transfer | PlumbFinal5 | Water Closet Seat | Water closet seat is required to be elongated and have an open front-UPC 408.2, 408.2.1 and 408.2.2 | | |
| 4/29/2014 | Transfer | PlumbFinal6 | ADA Requirements | Fixtures are not installed per ADA requirements-Per ANSI A1171.1 code | back shop | flush handle to be outside of wall |
| 4/29/2014 | Transfer | PlumbFinal7 | Backflow Preventer Testing | Backflow preventer shall be tested and properly tagged-UPC 603.1 | | |