Inspection #: 293993
Inspection Type: Final Electrical
Inspector: M.Green
Result: Approved
Comment: Please Call Jason before you show up 952-1104 Requested by: Brent Hovden 830-2523 brenth@redielectric.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
5/15/2014 EF1Correct Below Service.Max available fault current labelling per 110.24(A).
5/15/2014 EF1Correct Below Hangar lower 18" C1 D2 area.Can hangar door electric eyes be in the C1 D2 area?
4/23/2014 EF1Correct Below Branch circuit panels.Bond feeder conduits to panel enclosures.
4/23/2014 EF1Correct Below Panels.Boilers need 15A breakers.