| Date | Status | Code | Description | Ref | Location | Comments |
| 5/15/2014 | | EF1 | Correct Below | | Service. | Max available fault current labelling per 110.24(A). |
| 5/15/2014 | | EF1 | Correct Below | | Hangar lower 18" C1 D2 area. | Can hangar door electric eyes be in the C1 D2 area? |
| 4/23/2014 | | EF1 | Correct Below | | Branch circuit panels. | Bond feeder conduits to panel enclosures. |
| 4/23/2014 | | EF1 | Correct Below | | Panels. | Boilers need 15A breakers. |