Inspection #: 290898
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: WOULD LIKE TO SCHEDULE FINAL ELECTRICAL INSPECTION FOR PM ON 04/18/2014 POC: JASON SCHRECENGOST (907)952-1104 Requested by: KIRSTEN 261-3240 KIRSTEN.KING@REDIELECTRIC.COM

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
4/18/2014TransferEF1Correct Below Service.Max available fault current labelling per 110.24(A).
4/18/2014TransferEF1Correct Below Branch circuit panels.Bond feeder conduits to panel enclosures.
4/18/2014TransferEF1Correct Below Panels.Boilers need 15A breakers.