| Date | Status | Code | Description | Ref | Location | Comments |
| 3/26/2014 | Transfer | EF1 | Correct Below | | Panel B | Breaker locks for water heater must be fastened to the breakers. |
| 3/26/2014 | Transfer | EF1 | Correct Below | | Site lighting poles. | Ground wire needs to be #10 AWG to match current carrying conductors. |