Inspection #: 289199
Inspection Type: Final Mechanical
Inspector: J.Gadomski
Result: Correction
Comment: I can meet you in the loading dock of ak regional. Please call 10 minutes prior to arrival. Requested by: James Burton 7640953

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/14/2014TransferMechFinalSee commentsSee Inspector Comments2nd floor:Sterilization1. Per MOA Amendment - 23.10.104.1 – ‘Permits required. Any owner or authorized agent intending to construct, enlarge, alter, repair, move, demolish, or change the occupancy of a building, structure or portion thereof, or to erect, install, enlarge, alter, repair, remove, convert or replace any electrical, gas, mechanical or plumbing system, the installation of which is regulated by this code, or to cause any such work to be done, shall first make application to the building official and obtain the required permit unless work is specifically exempted by this code.’ – 2. Per 2009 MOA Amendment – Section 106.1 – ‘….No work shall be covered prior to the necessary inspection(s).’ There is no record of a rough-in DWV/Water piping tests and inspection.