Inspection #: 289131
Inspection Type: Final Electrical
Inspector: M.Green
Result: Partial
Comment: All items completed for final. Unable to correct ground wire to exterior site lighting poles . Will correct in spring when raceway is thawed. Requested by: Ken Smith 440-0005

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
3/20/2014TransferEF1Correct Below Panel BBreaker locks for water heater must be fastened to the breakers.
3/20/2014TransferEF1Correct Below   
3/20/2014TransferEF1Correct Below Site lighting poles.Ground wire needs to be #10 AWG to match current carrying conductors.
3/20/2014TransferEF1Correct Below 1st floor electric water heater.Label as to source of supply. Breaker locks.
3/20/2014TransferEF1Correct Below Main entry.Install chandalier.
3/20/2014TransferEF1Correct Below StairwellEM battery light needs to be on stairwell circuit.
3/20/2014TransferEF1Correct Below VariousBlank off switches for lights that are not to be installed.