Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 282479
Inspection Type: Final Electrical
Inspector: M.Green
Result: Partial
Comment: Contact Bob when on site 727-2002 Requested by: Bob Parsons 727-2002 bob@qealaska.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
2/10/2014TransferEF1Correct Below 1.ServiceMultiple service placcarding per 230.2(E).
2/10/2014TransferEF1Correct Below 2.ServiceFault current calc placcarding per 110.24(A).
2/10/2014TransferEF1Correct Below 3.TI panels.Placcarding showing circuit source per 408.4(B)
2/10/2014TransferEF1Correct Below 4.RTUsPlaccard to show circuits feeding
2/10/2014TransferEF1Correct Below 5.Exterior receptaclesChange to type WR.
2/10/2014TransferEF1Correct Below 6.ServiceLabels to show loads from each disconnect.
2/10/2014TransferEF1Correct Below 7.MDPs for Chilli's, Olive Garden, Mall W End.Placcard each to show where fed from.
2/10/2014TransferEF1Correct Below Services.Label per 230.2(E)
2/10/2014TransferEF1Correct Below   
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter