Inspection #: 280765
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: Final inspection for tenant spaces 102,103,109,west entrance, and restrooms/corridor. Please contact Bob @ 727-2002 when on site Requested by: Bob Parsons 727-2002 bob@qealaska.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
1/23/2014TransferEF1Correct Below 1.ServiceMultiple service placcarding per 230.2(E).
1/23/2014TransferEF1Correct Below 2.ServiceFault current calc placcarding per 110.24(A).
1/23/2014TransferEF1Correct Below 3.TI panels.Placcarding showing circuit source per 408.4(B)
1/23/2014TransferEF1Correct Below 4.RTUsPlaccard to show circuits feeding
1/23/2014TransferEF1Correct Below 5.Exterior receptaclesChange to type WR.
1/23/2014TransferEF1Correct Below 6.ServiceLabels to show loads from each disconnect.
1/23/2014TransferEF1Correct Below 7.MDPs for Chilli's, Olive Garden, Mall W End.Placcard each to show where fed from.