Inspection #: 277633
Inspection Type: Final Structural
Inspector: D.Blackburn
Result: Correction
Comment: Criterion General respectfully requests an AM inspection. Please call 30 minutes in advance for access. Ben Pierce 982-2396 Requested by: Ben Pierce 907 982 2396 benp@criteriongeneral.com Provide chiller unit spec's to design engineer for review and verification of conformance of units installed to loads of specified brand and model. Provide bearing surfaces of unit supports with correct area to repair bending deformation now present.Install support pier connections to WF beams per design details - plate to beam and double nuts.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
       