Inspection #: 266741
Inspection Type: Final Plumbing
Inspector: M.Gifford
Result: Correction
Comment: Please call September at 522-8126 for access info. Requested by: September Cassidy 907-522-8126 cassidysplumbing@aol.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
4/25/2014TransferPlumbFinalCommentsSee Inspector Commentslavslavs require ASSE1070
4/25/2014TransferPlumbFinal15Cleanout CapProvide an <u>approved</u> plug or cap for outside cleanout (Econo/Dollar plugs and Jim caps are not approved)- UPC 719.3, 707.1, 707.2 &nbsp;and local amendment UPC 719.1, UPC 719.5  
4/25/2014TransferPlumbFinal16Future Fixture CapsProvide an approved cap or plug for future plumbing-417.0shower drains 
4/25/2014TransferPlumbFinal17Backflow Preventer RequiredAn approved backflow preventer is required-UPC 602.2shopPVB required on hb drains in shop
4/25/2014TransferPlumbFinal5Water Closet SeatWater closet seat is required to be elongated and have an open front-UPC 408.2, 408.2.1 and 408.2.2  
4/25/2014TransferPlumbFinal6ADA RequirementsFixtures are not installed per ADA requirements-Per ANSI A1171.1 codeback shopflush handle to be outside of wall
4/25/2014TransferPlumbFinal7Backflow Preventer TestingBackflow preventer shall be tested and properly tagged-UPC 603.1  