Inspection #: 257703
Inspection Type: Electrical Service
Inspector: D.Rooney
Result: Correction
Comment: Please do not call at 10AM (important tele conf. scheduled at 10AM), BUT Please do call any other time FIRST for both questions and so I can be there. Requested by: Kim 444-6007

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/28/2013TransferES1Correct Belowsee inspectors commentat front of trailerinstall headbolt heater receptacle at front of trailer, on dedicated 20 amp circuit with in-use cover and GFCI protected
8/28/2013TransferES1Correct Belowsee inspectors commentat watermain#6 from panel to watermain must be unspliced or irreversibly spliced
8/28/2013TransferES1Correct Belowsee inspectors commentin panelback-fed main breaker must have hold down kit
8/28/2013TransferES1Correct Belowsee inspectors commentat dryerdryer cord and receptacle must be 4-prong, 4-wire grounding type plug with cable clamp at dryer
8/28/2013TransferES1Correct Belowsee inspectors commentin panelinstall #6 coppoer from neutral bus to ground bus