Inspection #: 257416
Inspection Type: Final Electrical
Inspector: D.Rooney
Result: Approved
Comment: Requested by: Jeff Summerville 250-0313

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/9/2013 EF1Correct Below naprovide muni approved pland
8/9/2013 EF1Correct Below in back room (high)provide access to water heater (disconnect required within sight)
8/9/2013 EF1Correct Below lobby areashow third party listing on all lights
8/9/2013 EF1Correct Below in south spacecounter be south entry not permitted to be cord connected, use chapter three wiring method
8/9/2013 EF1Correct Below at oven in south spaceshow third party listing on oven, disconnect required within sight
8/9/2013 EF1Correct Below both panelspanel schedules need more detail - not two circuits labeled alike
8/9/2013 EF1Correct Below behind counterall receptacles behind counter must be GFCI protected - including recptacles on wall behind counter
8/9/2013 EF1Correct Below freezer behind counterground prong broken off plug atfreezer
8/9/2013 EF1Correct Below at counterrefer undercounter marked-max overcurent 15 amps
8/8/2013 EF1Correct Below   