Inspection #: 257396
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: Please call so that building may be unlocked if inspection is after 10:00 AM building will be open. Requested by: Ken Smith 440-0005

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
2/13/2014TransferEF1Correct Below mechanical roomlabel air handler disconnects
2/13/2014TransferEF1Correct Below   
2/13/2014TransferEF1Correct Below Site lighting poles.Ground wire needs to be #10 AWG to match current carrying conductors.
2/13/2014TransferEF1Correct Below 1st floor electric water heater.Label as to source of supply. Breaker locks.
2/13/2014TransferEF1Correct Below Main entry.Install chandalier.
2/13/2014TransferEF1Correct Below VariousBlank off switches for lights that are not to be installed.
2/13/2014TransferEF1Correct Below StairwellEM battery light needs to be on stairwell circuit.
2/13/2014TransferEF1Correct Below   
2/13/2014TransferEF1Correct Below  RECPETACLE IN KITCHEN STORAGE ROOM NOT ENERGIZED
2/13/2014TransferEF1Correct Below  complete wiring and lights in stairwell
2/13/2014TransferEF1Correct Below by water softenersbod around water pressure tank and plastic water softer piping
2/13/2014TransferEF1Correct Below north side of exit doorsrecpetacle is not flush with trim plate
2/13/2014TransferEF1Correct Below  identify emergency lites on panel schedules
2/13/2014TransferEF1Correct Below pump roomlabel electrical panel (Panel A?)
8/2/2013TransferEF1Correct Below pnlproper designations.
8/2/2013TransferEF1Correct Below pnlsub feed breaker not labelled .
8/2/2013TransferEF1Correct Below troffersplates not screwed
8/2/2013TransferEF1Correct Below stairno em lt
8/2/2013TransferEF1Correct Below blr rmhang lt properly
8/2/2013TransferEF1Correct Below celingboxes cannot be supported by emt
8/2/2013TransferEF1Correct Below T-bar grid ceilings.SAome troffers need seismic wires.
8/2/2013TransferEF1Correct Below Troffer fixt..Not fastened to grid.
8/2/2013TransferEF1Correct Below T-bar ceilings.MC cable support wires need to tie to grid.
8/2/2013TransferEF1Correct Below Track lightingNeeds supportwires every 4ft.
8/2/2013TransferEF1Correct Below Kitchen ceiling.Complete cord reel or power pole rough-in.
8/2/2013TransferEF1Correct Below Exterior remote EMhead 
8/2/2013TransferEF1Correct Below Double doors to exterior.Remote ext head not coming on.
8/2/2013TransferEF1Correct Below AHUsWhere is listing label?
8/2/2013TransferEF1Correct Below VariousTrim plates missing.