Inspection #: 256291
Inspection Type: Final Zoning
Inspector: R.Novy
Result: Correction
Comment: Chuck York 351-4233 call to confirm timeZoning inspection-CCO not approved. Prior to approval:1. Provide an as-built2. See Community Planning regarding parking spaces. Currently there are 551 spaces provided and 576 are required 3. Corrections for Landscape Enlargement #1 page L102: -Provide 7 boulders within landscape islands where required -Provide 4 Paper Birch trees in the SW landscape island 4. Corrections for Landscape Enlargement #2 page L103: -Provide 5 boulders in the center landscape island as required -Provide 8 willows/alders in the NE corner of the perimeter landscape -Provide 20 shrubs in the center landscape island 5. Corrections for Landscape Enlargement #3 page L104: -Provide 6 boulders for the landscape islands directly in front of the building 6. Corrections for Landscape Enlargement #6 page L105: -(I will re-inspect for #6's requirements tomorrow and update this correction.) - Provide the 8' screening spruce trees along the highway required in the LS plan 7. Adjust the handicap parking: -Remove the word van painted on the asphalt on two of the handicap spaces -Swap "van accessible" signs to the other side of the post on two of the handicap spaces. -Provide "No Parking" signs on the van accessible lanes

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
       