Inspection #: 256244
Inspection Type: Final Structural
Inspector: D.Hickel
Result: Correction
Comment: PM please call 30 minutes b4 to meet on site Requested by: Brian Wesr 345-4043

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
3/20/2014TransferFNLSANC house #'sInstall house numbers using contrasting colors. House numbers to be clearly visible from the street. install address at street
3/20/2014TransferFNLSBNC HandrailsHandrails to be 34" - 38" above the stairs measured at the nose of the stair in a plumb line complete handrails at all stairs
3/20/2014TransferFNLSCNC GuardrailsGuardrails to be 36" above finish floor. 4" maximum opening Complete guards as required
3/20/2014TransferFNLSGFinal Structural OtherPlease correct the following: Complete firestop above ceilings at all rated wall assemblies.
3/20/2014TransferFNLSGFinal Structural OtherPlease correct the following: Bathrooms per ANSI 117.1
3/20/2014TransferFNLSGFinal Structural OtherPlease correct the following: door 105 to be 90 min