| Date | Status | Code | Description | Ref | Location | Comments |
| 8/2/2013 | Transfer | EF1 | Correct Below | | pnl | proper designations. |
| 8/2/2013 | Transfer | EF1 | Correct Below | | pnl | sub feed breaker not labelled . |
| 8/2/2013 | Transfer | EF1 | Correct Below | | troffers | plates not screwed |
| 8/2/2013 | Transfer | EF1 | Correct Below | | stair | no em lt |
| 8/2/2013 | Transfer | EF1 | Correct Below | | blr rm | hang lt properly |
| 8/2/2013 | Transfer | EF1 | Correct Below | | celing | boxes cannot be supported by emt |
| 8/2/2013 | Transfer | EF1 | Correct Below | | T-bar grid ceilings. | SAome troffers need seismic wires. |
| 8/2/2013 | Transfer | EF1 | Correct Below | | Troffer fixt.. | Not fastened to grid. |
| 8/2/2013 | Transfer | EF1 | Correct Below | | T-bar ceilings. | MC cable support wires need to tie to grid. |
| 8/2/2013 | Transfer | EF1 | Correct Below | | Track lighting | Needs supportwires every 4ft. |
| 8/2/2013 | Transfer | EF1 | Correct Below | | Kitchen ceiling. | Complete cord reel or power pole rough-in. |
| 8/2/2013 | Transfer | EF1 | Correct Below | | Exterior remote EMhead | |
| 8/2/2013 | Transfer | EF1 | Correct Below | | Double doors to exterior. | Remote ext head not coming on. |
| 8/2/2013 | Transfer | EF1 | Correct Below | | AHUs | Where is listing label? |
| 8/2/2013 | Transfer | EF1 | Correct Below | | Various | Trim plates missing. |
| 8/2/2013 | Transfer | EF1 | Correct Below | | mechanical room | label air handler disconnects |
| 8/2/2013 | Transfer | EF1 | Correct Below | | pump room | label electrical panel (Panel A?) |
| 8/2/2013 | Transfer | EF1 | Correct Below | | | identify emergency lites on panel schedules |
| 8/2/2013 | Transfer | EF1 | Correct Below | | north side of exit doors | recpetacle is not flush with trim plate |
| 8/2/2013 | Transfer | EF1 | Correct Below | | by water softeners | bod around water pressure tank and plastic water softer piping |
| 8/2/2013 | Transfer | EF1 | Correct Below | | | complete wiring and lights in stairwell |
| 8/2/2013 | Transfer | EF1 | Correct Below | | | RECPETACLE IN KITCHEN STORAGE ROOM NOT ENERGIZED |
| 8/2/2013 | Transfer | EF1 | Correct Below | | | |